BOMwiki the bill-of-materials encyclopedia

VAV Terminal Box Product

Overview

A VAV (variable air volume) terminal box is the lungs of a modern office or institutional building, sitting in every room's ceiling plenum and doing three jobs simultaneously: controlling how much conditioned air flows into that room, maintaining the room's temperature setpoint, and participating in the building's energy optimization. Instead of filling every room with a constant, full-speed stream of cold supply air (as a constant volume or CAV system does), VAV boxes modulate their intake damper to send only the airflow each room needs at that moment. When a room is cool or unoccupied, the damper closes and airflow drops to a minimum ventilation rate; when the room heats up, the damper opens and airflow increases. This dramatically cuts fan energy — a VAV system's fan power scales with the cube of airflow, so reducing average flow by even 20% halves the fan's energy consumption.

The box contains a Intake Damper & Actuator on the supply inlet, a Hot-Water Reheat Coil that can add warm water heating, an Airflow Measurement Sensor that measures actual flow, and a VAV Terminal Controller that orchestrates everything based on the room thermostat demand.

The modulating intake damper

The Intake Damper & Actuator is the heart of the terminal box: a set of four opposed airfoil Damper Blade arranged like a window blind, rotatable on a common Damper Shaft. When the blades are fully open, the plenum supply air flows straight through; when closed, flow is restricted. An Modulating Actuator, a 24 V proportional motor, drives the shaft to any position 0–100%. The Position Feedback potentiometer reports back the actual blade angle so the control loop knows where the damper is.

The VAV controller receives the room thermostat demand (a 0–10 V analog signal: 2 V = 18 °C, 8 V = 28 °C, etc.) and the Airflow Measurement Sensor feedback (0–10 V proportional to actual m³/s). If the room is too cold, the controller modulates the Modulating Actuator toward closed and opens the Reheat Control Valve hot-water valve to reheat the reduced airflow. If the room is too warm, the controller opens the damper and closes the reheat valve, allowing cool supply air to enter. Occupancy and setback rules can further limit maximum flow at night or on weekends.

Reheat coil and temperature control

The Hot-Water Reheat Coil is a small hot-water finned-tube coil downstream of the damper. Hot water from the building boiler (60–82 °C typical) circulates through the coil, and the supply airflow passes across its fins. The Reheat Control Valve is a proportional 2-way valve that modulates water flow (0–100%) in response to the controller. As room temperature falls, the controller opens the reheat valve, allowing more hot water to flow through the coil and warming the (already reduced) supply air. A Discharge Temperature Sensor in the discharge measures actual supply temperature and provides feedback, ensuring accuracy.

Airflow measurement and feedback

Many VAV boxes include a Airflow Measurement Sensor, a differential-pressure or anemometer transmitter in the discharge that measures the actual airflow in m³/s. This Airflow Measurement Sensor output tells the controller whether the damper is delivering the demanded flow or if blockage or leakage is occurring. This feedback allows the system to compensate for aging filters and balance adjustments automatically.

System-level pressure coordination

While individual VAV boxes modulate their dampers, the building's central air-handling unit or VAV fan section must maintain enough static pressure in the plenum to overcome the VAV box pressure drops and deliver the total system flow demanded by all boxes. A Static Pressure Sensor on some VAV boxes sends the ductwork static pressure up to a system controller, which adjusts the main AHU fan speed to maintain a setpoint plenum pressure (typically 100–150 Pa). This ensures all VAV boxes have sufficient supply pressure while keeping the AHU fan from over-pressurizing the system.

Physical installation

The Insulated Casing is a lightweight insulated box, typically 400 × 400 × 300 mm, designed to sit in the ceiling plenum above drop ceilings. The Supply Inlet Collar accepts bolted connection to the plenum supply ductwork (typically 300–400 mm diameter round or rectangular duct). The Discharge Collar connects via short Discharge Flex Duct ductwork and Duct Vibration Hanger isolation hangers to the room's supply registers (typically one or two diffusers in the ceiling). The Access Service Door allows field technicians to access the damper and coil for cleaning or balancing.

Control integration and commissioning

The Room Thermostat is wall-mounted in the occupied space at eye level, typically with a dial or digital display. Users set the desired temperature setpoint; the thermostat generates a 0–10 V analog signal (or BACnet property) representing how far the space is from setpoint, and this feeds the VAV Terminal Controller on the VAV box. More advanced systems integrate all room thermostats into a building-wide BACnet or LON network, allowing a central BMS to override individual room setpoints for energy-conservation schedules, demand-response events, or system-level optimization.

Commissioning is critical: each VAV box's damper and reheat valve must be calibrated so the controller knows the exact 0–100% range; airflow sensor output is verified against a calibrated anemometer or pitot tube; and the interaction between damper modulation and reheat sequencing is tested to ensure there is no hunting (oscillation) or lag. A badly commissioned VAV system will waste energy and fail to maintain room comfort.

Advantages and limitations

VAV systems excel at partial-load operation: as occupancy and cooling demand vary throughout the day, VAV boxes automatically adjust supply flow, cutting fan energy significantly. However, VAV requires much more commissioning and field balancing than constant-volume systems. Reheat, while necessary for room-by-room control, does represent a form of simultaneous heating and cooling (cool air from the AHU's cooling coil is reheated in the VAV box) that is less energy-efficient than a more granular zone design. Modern best practices use demand-controlled ventilation (CO₂ sensors) to reduce minimum ventilation flow when rooms are unoccupied, and enthalpy-based economizer logic in the AHU to minimize reheat need during mild weather.

Build & assembly graph

expand / collapse · shared sub-assemblies converge · links to related products · est. labour
product / assembly shared across products atomic part related product

Tap an assembly to expand/collapse · tap a part to open it · use “Open page” for any node · drag to pan, scroll to zoom.

Bill of materials

8 top-level lines · 39 rows shown · 123 parts total · indented to 3 levels
# Item / sub-assembly Part no. Qty/assy Ext. qty Parts Type
1 Insulated Casing 4 parts vav-box-casing 1 7 assembly
1.1 Structural Frame vav-box-frame 1 part
1.2 Sheet Metal Panel sheet-panel 4 part
1.3 Thermal Insulation vav-box-insulation 1 part
1.4 Access Service Door vav-box-access-door 1 part
2 Intake Damper & Actuator 5 parts vav-box-damper-section 1 8 assembly
2.1 Damper Blade vav-box-damper-blade 4 part
2.2 Damper Shaft vav-box-damper-shaft 1 part
2.3 Modulating Actuator vav-box-damper-actuator 1 part
2.4 Actuator Linkage vav-box-damper-linkage 1 part
2.5 Position Feedback vav-box-damper-feedback 1 part
3 Mixing Chamber & Inlet 3 parts vav-box-mixing-chamber 1 3 assembly
3.1 Supply Inlet Collar vav-box-inlet-collar 1 part
3.2 Inlet Flow Ring vav-box-inlet-ring 1 part
3.3 Mixing Baffle vav-box-mixing-baffle 1 part
4 Hot-Water Reheat Coil 5 parts vav-box-reheat-coil 1 6 assembly
4.1 Reheat Coil Tubes vav-box-coil-tubes 1 part
4.2 Coil Fin Pack vav-box-coil-fins 1 part
4.3 Coil Header vav-box-coil-header 2 part
4.4 Reheat Control Valve vav-box-coil-valve 1 part
4.5 Water Strainer vav-box-coil-strainer 1 part
5 Airflow Measurement Sensor 2 parts vav-box-airflow-sensor 1 2 assembly
5.1 Flow Measurement Probe vav-box-flow-probe 1 part
5.2 Flow Transmitter vav-box-flow-transmitter 1 part
6 Discharge Ductwork Collar 3 parts vav-box-outlet-duct 1 4 assembly
6.1 Discharge Collar vav-box-discharge-collar 1 part
6.2 Discharge Flex Duct vav-box-discharge-flex 1 part
6.3 Duct Vibration Hanger vav-box-duct-hanger 2 part
7 Control & Sensing System 5 parts vav-box-controls 1 92 assembly
7.1 VAV Terminal Controller 4 parts vav-box-controller 1 85 assembly
7.1.1 Bare PCB pcb-bare 1 part
7.1.2 Microcontroller mcu 1 part
7.1.3 SMD Passive (R/C/L) smd-passives 80× 80 part
7.1.4 Connector connector 3 part
7.2 Room Thermostat vav-box-room-thermostat 1 part
7.3 Discharge Temperature Sensor vav-box-temp-sensor 1 part
7.4 Static Pressure Sensor vav-box-pressure-sensor 1 part
7.5 Connector connector 4 part
8 Access Service Door vav-box-access-door 1 part

Sourcing — likely vendors

Companies that make this · indicative price $100–$20k · MOQ & lead are typical
VendorHQSpecialtyMOQLead time
🇺🇸Carrier
carrier.com ↗
Palm Beach Gardens, US HVAC 500 units 8–14 wks
tranetechnologies.com ↗ Davidson, US HVAC 500 units 8–14 wks
🇯🇵Daikin
daikin.com ↗
Osaka, JP HVAC 500 units 8–14 wks
🇺🇸Lennox
lennox.com ↗
Richardson, US HVAC 500 units 8–14 wks
johnsoncontrols.com ↗ Milwaukee, US Building systems 500 units 8–14 wks

1,062-word article