Dry-Type Transformer

Product

Overview

A Dry-Type Transformer performs the same voltage transformation as an oil-filled unit but uses solid epoxy resin and air instead of insulating oil. That single change makes it suited to indoor and fire-sensitive sites: hospitals, high-rise buildings, ships, data centres, tunnels and chemical plants, where an oil fire or a spill would be unacceptable. The cast-resin version, the most common type for medium-voltage distribution, encases each high-voltage coil in a void-free epoxy body that is self-extinguishing and does not leak.

Ratings typically run from a few hundred kVA up to about 25 MVA at distribution voltages of 6.6, 11, 22 or 33 kV. Because there is no oil, there is no conservator, no Buchholz relay and no oil sampling regime, which simplifies installation and maintenance. The trade-offs are a higher cost per kVA, a lower overload capacity and audible-noise characteristics that need attention in occupied spaces.

Magnetic core

The Magnetic Core is built from grain-oriented silicon-steel laminations in the same way as an oil transformer, with limbs and yokes forming the magnetic loop. Step-lap joints are used to reduce the localised flux crowding that causes hum, since these units often sit close to people. Clamping frames and tie rods hold the stack, and anti-vibration pads under the core feet stop magnetostrictive hum reaching the base frame and the building structure. The core is earthed once through the earthing strap.

Cast-resin windings

The winding assembly is what defines a cast-resin unit. The high-voltage coil is layer-wound from enamelled conductor with inter-layer film, reinforced with glass-fibre mesh, and then cast in epoxy resin under vacuum. The vacuum step is essential: it pulls air out of the casting so no voids remain, because a void would ionise under voltage and start partial discharge that erodes the insulation. An embedded field-grading shield smooths the electric field at the coil ends to keep partial discharge below the IEC limit, usually under 10 pC.

The low-voltage coil is wound from conductor foil rather than wire. A full-width foil makes every turn carry the same current along its whole height, which gives even heating and strong resistance to the axial forces of a short circuit. The foil layers are insulated by film and impregnated with resin. Glass-fibre spacer bars set the cooling air gap between the LV and HV coils.

Resin and dielectric system

The resin system replaces oil as the bulk dielectric. The epoxy resin is mixed with a hardener and heavily loaded with silica filler so the cured body conducts heat away from the conductors and expands at nearly the same rate as the copper or aluminium inside it. Matching the thermal expansion matters because the coil is cycled through wide temperature swings in service, and a mismatch would crack the casting. Coils are formed in machined moulds and cured at temperature to develop full cross-linking and Class F or Class H thermal rating.

Enclosure and cooling

With no oil to carry heat to external radiators, a dry-type transformer is cooled directly by air over the coil surfaces. The enclosure and cooling system uses vertical air ducts through and around the coils so convection draws cool air up past the windings. In its natural-air (AN) mode the unit relies on convection alone. Adding forced-air fans gives the AF rating, raising continuous capacity by 25 to 40 percent for peak periods. The sheet-steel enclosure carries ventilation louvres and guard mesh to give an ingress-protection rating from IP21 up to IP54 while still admitting airflow.

Tap setting, terminations and protection

Ratio is set by an off-circuit tap arrangement: bolted tap links on a tap busbar are moved when the transformer is de-energised. The terminations bring the HV connection in through stand-off insulators and take the LV current out on busbars, with a removable neutral link for earthing.

Protection is thermal rather than gas-based. PT100 sensors cast into the LV coils feed a temperature controller that stages the fans, raises an alarm and trips the unit if a coil exceeds its class limit, with a backup cutoff behind it. The controller and fan contactors sit in the control cabinet.

Standards and application

Cast-resin transformers are built and tested to IEC 60076-11 and IEEE C57.12.01, which set the partial-discharge, climatic (C), environmental (E) and fire-behaviour (F) classes. The top fire class, F1, requires the unit to be self-extinguishing and to emit limited smoke, which is the property that lets a dry-type unit sit directly inside an occupied building where an oil-filled transformer would need a separate fire-rated vault.

Bill of materials for Dry-Type Transformer

9 top-level lines as of r51233
# Item / sub-assembly Part no. Qty/assy Ext. qty Parts Type
1 Magnetic Core 7 parts dry-type-transformer-core 1× 1 0 assembly
2 Cast-Resin Winding Assembly 5 parts dry-type-transformer-windings 1× 1 0 assembly
3 Resin & Dielectric System 5 parts dry-type-transformer-resin-system 1× 1 0 assembly
4 Enclosure & Air Cooling 6 parts dry-type-transformer-enclosure-cooling 1× 1 0 assembly
5 Off-Circuit Tap Setting 3 parts dry-type-transformer-detc 1× 1 0 assembly
6 Terminations 5 parts dry-type-transformer-terminations 1× 1 0 assembly
7 Thermal Protection & Monitoring 5 parts dry-type-transformer-protection 1× 1 0 assembly
8 Base Frame & Mounting 5 parts dry-type-transformer-mounting 1× 1 0 assembly
9 Control Cabinet 5 parts dry-type-transformer-control-cabinet 1× 1 0 assembly

1,005-word article